The A5364CA is a low-current, CMOS circuit providing all of the required features for an ionization-type smoke detector. A networking capability allows as many as 125 units to be interconnected so that if any unit senses smoke, all units will sound an alarm. In addition,special features are incorporated to facilitate alignment and test of the finished smoke detector. This device is designed to comply with Underwriters Laboratories Specification UL217.
The internal oscillator and timing circuitry keeps standby power to a minimum by powering down the device for 1.66 seconds and sensing smoke for only 10 ms. Every 24 on/off cycles, a check is made for low battery condition. By substituting other types of sensors, or a switch for the ionization detector, this very-low power device can be used in numerous other battery-operated safety/security applications.
The A5364CA is supplied in a low-cost, 16-pin dual in-line plastic package. It is rated for continuous operation over the temperature range of 0°C to +50°C. Similar devices. with an internal timer to allow for a period of reduced sensitivity ("hush"), are available as the A5368CA.
|
|
*Interconnect Up to 125 Detectors*Piezoelectric Horn Driver*Guard Outputs for Detector Input*Pulse Testing for Low Battery*Power-ON Reset*Internal Reverse Battery Protection*Built-In Hysteresis Reduces False Triggering*Temporal Horn Pattern
|
Supply Voltage Range,
VDD ........................ -0.5 V to +15 V
Reverse Battery (10.5 V) ........... 20 s
Input Voltage Range,
VIN ................ -0.3 V to VDD + 0.3 V
Input Current, IIN .................. 10 mA
Operating Temperature Range,
TA ........................... 0°C to +50°C
Storage Temperature Range,
TS ...................... -55°C to +125°C